14Z1B04-1000, line choke 17.3A, Uk = 4%
CHF 185.44 excl.
line choke with a rated current 17.3A, rated voltage 3 x 400 (max. 550)Vac and Voltage drop Uk 4%
Available: Delivery time approx. 8 weeks
F6 Combivert Drive accessories, line choke:
- Dimensions (WxHxD) 148x77.0x145mm
- Rated current 17.3A
- Maximum current 29.7A
- Rated voltage 3 x 400 (max. 550)Vac
- Voltage drop Uk 4%
- Connection 3 phases 4,0mm2
- Connection PE M4
- Power losses 69W
- Protection class IP20
The use of a line choke with Uk = 4% prevents premature aging of the electrolytic capacitors and improves the active power consumption of the controller.
Certifications: CE, UR
A line choke must be used for continuous operation (S1) with a load > 60% or a rated motor power of more than 55 kW.
Item no. | 2000-2002 |
Manufacturer | KEB |
Weight | 2.450 kg |
Availability | on order |
Voltage drop uk | 4% |
Choke rated current | 17.3 amps |